Dandy Farm / Power Service
Model #PDC-FF
EEMAC 3R Enclosure
Specifically designed as a service entrance rated, pad mount, weatherproof power distribution centre complete with CT/PT section and load side terminals
Ideal for supply of various feeders to multiple locations (as per CEC #14-100)
Standard loadterminals are (8) #6-250 Cu/Al mechanical lugs, (8) #6-250 provisions, and 2) #2-600 provisions per phase + neutral & (8) #10-2/0 & (4) #6-250 ground lugs
Compact size complete with oversized drip hood and padlockable doors, complete with 3 point padlockable stainless steel handle and 4" snow kick
Acceptable for bottom entry. Mounting flange turned in all around for aesthetics and durability.
Main fused section is service entrance rated complete with lockable doors and neutral/bonding facility
CT section has rear CT/PT mounting pan and has hinged sealable and padlockable cover
Safety soft machine formed corners on doors and hood
Standard size is 250-1200A, single or three phase, to 600V
CSA certified assembly
NOTE
Consult factory for various options available
Utility meter socket, line side terminal box and TV/Telephone cell optional